Emergency Mixing Valve System with Temperature Override Protection in Cabinet

Eye Wash - TA-350-LF-STSTL-EXP

DURA-trol® solid bimetal thermostat directly linked to valve porting, DURA-trol® is highly responsive and cannot be damaged by extremes in temperature. Primary valve can be set to the correct temperature for the application. Locking temperature regulator to prevent accidental movement set for 85ºF (29ºC), Primary mixing valve will close down on failure of cold water supply Primary Mixing Valve with special internal cold water bypass capable of 4 GPM (15 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply. Adjustable high temperature limit stop set for 90ºF (32ºC) dial thermometer (range 0 to 140°F, -10 to 60°C), Straight checkstops on inlets, Secondary Thermostatic Control factory locked @ 90°F, 32°C(adjustable from 40°F to 100°F, 4°C to 32°C) to allow cold water to enter the outlet side of the primary mixing valve. Rough bronze finish Mounted in cabinet with hinged door and lock To determine the amount of Hot Water needed to maintain a steady outlet temperature for 15 minutes, click Hot Water Requirements. This guide is not meant to be used as a means to size the hot water heaters but rather to illustrate consumption.
Repair Kits
VALVE REPAIR KIT - KIT R/TA/M
CHECK REPAIR KIT - KIT 4/LVC
Specification
Inlets 3/4"
Maximum Flow(GPM) 10
Minimum Flow(GPM) 2
Outlet 3/4"
Weight (pounds) 50
Options
Baked White Exposed Cabinet BWE-EXP
Baked White Recessed Cabinet BWE-REC
Inlet Thermometers IT
Stainless Steel Exposed Cabinet STSTL-EXP
Stainless Steel Recessed Cabinet STSTL-REC
Viewport in Cabinet Door VIEW
Megatron Nucleus Installed